Huawei · Outdoor Cabinets & Enclosures

Huawei outdoor cabinets — ICC330, ICC710, TP48200A, APM30H and the PowerCube family

Huawei outdoor cabinets reach us in three forms of enquiry: a PowerCube 1000 integrated cabinet named by its full code (ICC330-H1-C4, ICC360-HA1-C1) for a new power site; a TP48200A outdoor power cabinet with rectifiers and SMU for a solar or hybrid rollout, typically with a 12 kW rectifier set; or an APM30H / TMC11H / IBBS200 stack to extend or replace a BTS3900A site. The table lists all three families with the climate variant, equipment space and battery fit where Huawei's own documentation states them, and says "confirmed per quotation" where it does not.

How to read these part numbers

ICC is the PowerCube 1000 integrated cabinet (Huawei's manuals expand it as integrated controller and converter; dealers write "integrated communication cabinet") and ESC the energy-storage cabinet that pairs with it. The number is a size series: ICC330 / ESC330 are 1600 × 650 × 650 mm, ICC710 / ESC710 are 1925 × 900 × 950 mm, ICC800 / ESC800 are 2000 × 800 × 800 mm. The letters that follow describe the climate units, read from the specification tables rather than defined by Huawei: H is a heat exchanger on the equipment bay (HEX100 at 150 W/K or HXC300S at 250 W/K), A a DC air conditioner (PC500D 600 W, PC1000D 1100 W, PC1500D-1 1500 W), D direct ventilation and N natural cooling — so H1 is heat exchanger only, HA1 heat exchanger plus air-conditioned battery bay, HD1 heat exchanger plus ventilated battery bay. The C-number is a configuration code that tracks equipment space and battery count (C8 is 22U with no internal battery; C10 and C5 are 8U with four lithium modules; C7 is 14U with twelve). TP48 is −48 V telecom power with the rated current after it (TP48200A = 200 A, TP48300A = 300 A); the two digits after the H/D/HX/HT/DT prefix track cabinet height in decimetres (HX09 = 900 mm, D14 = 1400 mm, H15 = 1500 mm, HT19 = 2030 mm including base) and the final A1/A5/C3/D1 is a configuration code. APM30H is the heat-exchanger outdoor power cabinet for BTS3900A and DBS3900 sites, with Ver.C/D/E hardware revisions; TMC11H is the matching transmission cabinet; IBBS200D and IBBS200T are the battery cabinets, D for direct ventilation and T for a built-in air conditioner.

Catalogue

Equipment reference

90 of 90 items
Part NumberModel / DesignationCompatibilityBand / InterfaceConditionLead TimeQuote
APM30APM30 outdoor power cabinet (earlier generation)Huawei distributed base stations; 50 / 100 / 200 Ah extension battery cabinets600 × 700 × 480 mm excl. 200 mm base; <55 kg; DC output ≤3200 W, 0–60 A; internal batteries 12–36 Ah; IP55; −40 to +45 °C (heater below −20 °C)On enquiryOn enquiry
APM30HAlso: Ver.C, Ver.D, Ver.EAPM30H outdoor power cabinet for BTS3900A / DBS3900 sitesBBU3900 / BBU5900, BTS3900A, DBS3900 / DBS5900; AC input to −48 V DC700 × 600 × 480 mm excl. base; <76.5 kg excl. user equipment; heat exchanger with circulation fans; IP55; 220 V single-phase or 220 / 380 V three-phase variantsOn enquiryOn enquiry
APM5930(AC)APM5930 outdoor power cabinet, AC input, heat exchanger with thermosiphonDBS5900 with BBU5900 / BBU3910; EPU05A-11 (220 V AC) or EPU05A-12 (110 V AC) power system; optional EPU02D-021000 × 600 × 480 mm, base 200 × 600 × 434 mm; ≤73 kg excl. BBU, transmission and batteries; 5U customer space; heat dissipation 2500 W at 50 °C; IP55; 220 V AC single- or three-phase, 110 / 120 V AC dual-live-wire; −40 to +50 °C (AC heater below −20 °C)On enquiryOn enquiry
APM5930(DC)APM5930 outdoor cabinet, −48 V DC input, heat exchanger with thermosiphon (Ver.A, WD2B2CTMC / 02115551)DBS5900 with BBU5900 / BBU3910; DCDU16D (−48 V) or EPU02D-02 (−57 V) in customer space1000 × 600 × 480 mm, base 200 × 600 × 434 mm; ≤55 kg excl. BBU and transmission; 5U customer space; heat dissipation 2500 W at 50 °C; IP55; −38.4 to −57 V DC; −40 to +50 °COn enquiryOn enquiry
BTS3900AAlso: RFC / APM30H configurationsBTS3900A outdoor macro base-station cabinetBBU3900 / BBU5900; RRU / WRFU; APM30H, TMC11H, IBBS200 stackable700 × 600 × 480 mm per cabinet; 91–127 kg by configuration; RFC direct ventilation; IP55; −40 to +50 °C incl. solar radiationOn enquiryOn enquiry
BTS3900ALBTS3900AL outdoor macro base-station cabinet with integrated battery spaceBBU3900; WRFU / RRU; transmission equipment1925 × 770 × 750 mm incl. base; 550 kg incl. base and full batteries; IP55; −40 to +50 °COn enquiryOn enquiry
ESC300-N1PowerCube 1000 ESC300 outdoor battery cabinet, natural coolingS1 / S2 solar and V300R006 configurations; SCB-A / SCB-A1 / DCB-A / DCB-A1 lead-acid; up to 4 cabinets in S1One string max 800 Ah per cabinet; natural cooling; IP23; −10 to +40 °C (−10 to +45 °C with TCB-A) with solar radiationOn enquiryOn enquiry
ESC330-A2PowerCube 1000 ESC330 outdoor battery cabinet, DC air-conditioned, A2Pairs with ICC330-HA1-C1 or ICC330-H1-C2 (G2 grid hybrid); ESU-A2400Wh lithiumICC330-series housing; DC air-conditioned; system ESU-A capacity up to 600 Ah with ICC330-HA1-C1; IP55; 0 to +50 °C with solar radiation (−20 °C with pre-heat)On enquiryOn enquiry
ESC330-A6PowerCube 1000 ESC330 outdoor battery cabinet, DC air-conditionedPairs with ICC330 cabinets; ESM-48100B1/B2, ESM-48150B11600 × 650 × 650 mm; <110 kg; PC1500D-1 1500 W DC air conditioner; max 7 lithium modules; IP55; 0 to +45 °COn enquiryOn enquiry
ESC330-D2PowerCube 1000 ESC330 outdoor battery cabinet, direct ventilation, D2Pairs with ICC330-H1-C2 (G4 grid hybrid, roof site); TCB-C lead-acidICC330-series housing; direct ventilation; TCB-C max 680 Ah; IP34On enquiryOn enquiry
ESC330-D3PowerCube 1000 ESC330 outdoor battery cabinet, direct ventilation, D3Pairs with ICC330-H1-C2 or ICC330-HD1-C1 in S1 / S2 solar systems; ESM-4850A1 lithiumICC330-series housing; direct ventilation; system ESM-4850A1 up to 1600 Ah (S2, 32 × 50 Ah); IP34; 0 to +40 °C (install under the PV structure)On enquiryOn enquiry
ESC330-D6PowerCube 1000 ESC330 outdoor battery cabinet, direct ventilationPairs with ICC330 cabinets; ESM lithium modules1600 × 650 × 650 mm; <110 kg; direct ventilation; max 7 lithium modules; IP34; 0 to +45 °COn enquiryOn enquiry
ESC710-A1PowerCube 1000 ESC710 outdoor battery cabinet, DC air-conditioned, lead-acidPairs with ICC710 cabinets; FCB-A1925 × 900 × 1105 mm; <295 kg; PC1000D 1100 W DC air conditioner; 2 strings × 650 Ah; IP55; −10 to +45 °COn enquiryOn enquiry
ESC710-D2PowerCube 1000 ESC710 outdoor battery cabinet, direct ventilationPairs with ICC710 cabinets; FCB-A1925 × 900 × 1105 mm; <240 kg; direct ventilation; 2 strings × 650 Ah; IP34; −10 to +40 °COn enquiryOn enquiry
ESC800-A1PowerCube 1000 ESC800 outdoor energy-storage cabinet, DC air-conditionedPairs with ICC800-A1-C22000 × 800 × 800 mm; ≈250 kg empty; max 20 × 3U lithium modules; DC air conditioner; IP55; 0 to +45 °COn enquiryOn enquiry
IBBS200DAlso: IBBS200TIBBS200 outdoor battery cabinets — IBBS200D direct ventilation, IBBS200T built-in TECBackup for APM30H / BTS3900A / DBS3900 outdoor sites700 × 600 × 480 mm, base 200 × 600 × 480 mm; IBBS200D <50 kg, IBBS200T <70 kg (without batteries); 48 V 50 / 100 Ah or 92 / 184 Ah per cabinet (12 V 92 Ah block ≈33.5 kg); IBBS200D direct ventilation, −40 to +45 °C (heating film below −20 °C); IBBS200T TEC cooler, IP55, −20 to +50 °COn enquiryOn enquiry
IBBS700DIBBS700D outdoor battery cabinet, direct ventilation3900-series outdoor base stations needing long backupBuilt-in battery groups up to 700 Ah per cabinet; direct ventilation; dimensions and weight confirmed per quotationOn enquiryOn enquiry
IBBS700TIBBS700T outdoor battery cabinet, built-in air conditioner3900-series outdoor base stations needing long backup in hot climatesBuilt-in battery groups up to 700 Ah per cabinet; built-in air conditioner for high-temperature operation; dimensions and weight confirmed per quotationOn enquiryOn enquiry
ICC1000-A1-E1iSitePower ICC1000 large outdoor integrated cabinet, DC air-conditioned (iSitePower Integrated Smart Site ICC1000-A1-E1, BOM 01075363)iSitePower smart site for enterprise / transport sites; ETP48400-C3B1 power subrack; ESM-48100B1 / ESM-48100A8 lithium; optional PV, generator and M48500N1 modules2100 × 900 × 1200 mm incl. 200 mm base; <520 kg excl. PSUs and batteries; 30U lithium battery space; 12U customer space at ≤980 mm depth or 24U at ≤480 mm; up to 4 × PC1500D-1 (01075363) or 4 × PC3000D-2 (-001 / -002) DC air conditioners plus DC heater; IP55; bottom cabling; 85–300 V AC inputOn enquiryOn enquiry
ICC310-H1-C2PowerCube 1000 ICC310 outdoor integrated cabinet, heat exchangerPowerCube 1000 (V300R006); DCDU-400AN1 distribution1825 × 700 × 885 mm, base 100 × 700 × 650 mm; ≈200 kg; 26U customer space; heat exchanger 1800 W at 15 °C rise; IP55, Class C; ≤65 dBA at 1.5 m; −20 to +50 °C with solar radiationOn enquiryOn enquiry
ICC330-A3PowerCube 1000 ICC330 outdoor cabinet, DC air-conditioned (ICC330-A3-C1, BOM 01075381)PowerCube 10001.6 m class ICC330 housing, 650 × 650 mm footprint; air-conditioned; per-code weight and U space confirmed per quotationOn enquiryOn enquiry
ICC330-A6-F1PowerCube 1000 ICC330-A6-F1 outdoor battery cabinet, DC air-conditioned, 5-layer (BOM 01074335)PowerCube 1000 solution tables1600 × 650 × 650 mm (H × W × D); 5 horizontal battery layers; DC air conditioner; bottom cabling; 48 V battery group up to 750 AhOn enquiryOn enquiry
ICC330-H1-C2PowerCube 1000 ICC330 outdoor equipment cabinet, heat exchanger, config C2PowerCube 1000 S1 / S2 solar and G2 / G4 grid solutions; pairs with ESC330-D2, ESC330-D3, ESC330-A2, ESC300-N1 or ESC710-D2 battery cabinets650 × 650 × 1600 mm class; HEX 150 W/K; 21U customer space; DCDU-400AN2, 400 A; up to 8 × S4850G1 solar modules (S2); IP55; −20 to +45 °C (S1/S2) or 0 to +45 °C (G4) with solar radiationOn enquiryOn enquiry
ICC330-H1-C4PowerCube 1000 ICC330 outdoor hybrid power cabinet, heat exchanger, config C4 (BOM 01074418)PowerCube 1000; pairs with ESC330 battery cabinets1600 × 650 × 650 mm (H × W × D); controller and distribution unit included; 400 A max DC; heat exchanger cooling; BOM 01074418 / 01074418-001On enquiryOn enquiry
ICC330-H1-C5PowerCube 1000 ICC330 outdoor hybrid power cabinet, heat exchanger, config C5PowerCube 1000; separate equipment and battery areas1600 × 650 × 650 mm (H × W × D); 400 A max DC; heat exchanger cooling; 19-inch; IP55; RAL 7035On enquiryOn enquiry
ICC330-H1-C6PowerCube 1000 ICC330 outdoor hybrid power cabinet, heat exchanger, config C6 (BOM 01075071)PowerCube 10001600 × 650 × 650 mm (H × W × D); 400 A max DC; heat exchanger cooling; BOM 01075071On enquiryOn enquiry
ICC330-H1-C8PowerCube 1000 ICC330 outdoor equipment cabinet, heat exchanger, no internal batteryR4875G5 / R4850G5 / R4850G2 rectifiers; batteries in a separate ESC3301600 × 650 × 650 mm (810 mm incl. door); <100 kg; 22U; HXC300S heat exchanger 250 W/K; IP55; −20 to +45 °C with solar loadOn enquiryOn enquiry
ICC330-HA1-C1PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air-conditioned battery bay, config C1 (BOM 01073479)PowerCube 1000 G2 grid-hybrid; ECC500S controller; up to 8 × R4850S1 / R4850G2 / R4850N2; ESU-A2400Wh lithium; extends with ESC330-A2650 × 650 × 1600 mm class; equipment bay HEX 150 W/K, battery bay PC500D DC air conditioner; 7U customer space; ESU-A max 400 Ah (600 Ah with ESC330-A2); DCDU-400AN2, 400 A; IP55; 0 to +45 °C with solar radiation (−20 °C with pre-heat box)On enquiryOn enquiry
ICC330-HA1-C10PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air-conditioned battery bayR4875G5 / R4850G5 / R4850G2; ESM-48100B1/B2, ESM-48150B1 lithium1600 × 650 × 650 mm; <100 kg; 8U; HEX100 150 W/K + PC500D 600 W DC air conditioner; max 4 lithium modules; IP55; 0 to +45 °C (−20 °C with heater)On enquiryOn enquiry
ICC330-HA1-C4PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air-conditioned battery bay, config C4PowerCube 1000 S2 solar + diesel; ECC500S; R4850G2 / R4850N2 rectifiers; ESM-4850A1 lithium650 × 650 × 1600 mm class; equipment HEX 150 W/K, battery PC500D 600 W DC air conditioner; 7U customer space; ESM-4850A1 up to 250 Ah; DCDU-400AN2; IP55; 0 to +45 °C with solar radiationOn enquiryOn enquiry
ICC330-HA1-C6PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air conditioner, config C6Huawei hybrid site power, 220/380 V AC three-phase input; lithium battery bayICC330 housing; 400 A; PDU2000 distribution unit; lithium battery space with DC heater box, door, water and temperature/humidity sensorsOn enquiryOn enquiry
ICC330-HA1-C7PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air conditioner, config C7PowerCube 1000 grid and diesel configurations; controller and distribution unit included1600 × 650 × 650 mm (H × W × D); 400 A max DC; heat exchanger and DC air conditionerOn enquiryOn enquiry
ICC330-HA1-C9PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + DC air conditioner, config C9 (BOM 01075380)PowerCube 1000 grid and diesel configurations1600 × 650 × 650 mm (H × W × D); 400 A max DC; heat exchanger and DC air conditionerOn enquiryOn enquiry
ICC330-HD1-C1PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + direct-ventilation battery bay, config C1PowerCube 1000 S1 pure-solar; ECC500S; up to 8 × S4850G1; combines with ESC330-D3 and ESC300-N1 / ESC710-D2650 × 650 × 1600 mm class; equipment HEX 150 W/K, battery direct ventilation; 7U customer space; DCDU-400AN2, 400 A; IP55 equipment / IP34 battery; −20 to +45 °C with solar radiationOn enquiryOn enquiry
ICC330-HD1-C2PowerCube 1000 ICC330 outdoor hybrid power cabinet, heat exchanger + direct ventilation, config C2 (BOM 01074334)PowerCube 10001600 × 650 × 650 mm (H × W × D); 400 A max DC; equipment bay heat exchanger, battery bay direct ventilation; BOM 01074334 / 01074334-001On enquiryOn enquiry
ICC330-HD1-C5PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + direct-ventilation battery bayR4875G5 / R4850G5 / R4850G2; ESM-48100B1/B2, ESM-48150B1 lithium1600 × 650 × 650 mm; <90 kg; 8U; HEX100 150 W/K + direct ventilation; max 4 lithium modules; IP55 equipment bay / IP34 battery bay; 0 to +45 °COn enquiryOn enquiry
ICC330-HD3-C4PowerCube 1000 ICC330 outdoor integrated cabinet, heat exchanger + direct-ventilation battery bay, config C4PowerCube 1000; hybrid / solar site power1600 × 650 × 820 mm incl. door, base 100 × 650 × 650 mm; ≈180 kg; 8U; equipment bay heat exchanger 1000 W at 15 °C rise, battery bay direct ventilation; 2 × FCB-B strings, 100 or 150 Ah each; IP55 equipment / IP34 battery; −10 to +50 °C with solar radiationOn enquiryOn enquiry
ICC350-H1-C1PowerCube 1000 ICC350 compact outdoor cabinet, heat exchanger, 1 mPowerCube 1000 (V300R006)1000 × 650 × 700 mm incl. base (base 100 × 650 × 650 mm); ≈90 kg; 8U customer space; heat exchanger 1000 W at 15 °C rise; IP55, Class C; −20 to +50 °C with solar radiationOn enquiryOn enquiry
ICC350-H1-C5PowerCube 1000 ICC350 compact outdoor hybrid power cabinet, heat exchanger, config C5 (BOM 01075032)PowerCube 1000 (BOM 01075032 / 01075032-001); DCDU400-AN2 embedded power650 × 650 × 1000 mm (W × D × H); 48 V / 400 A; heat exchangerOn enquiryOn enquiry
ICC360-HA1-C1Huawei ICC360 outdoor integrated cabinet, heat exchanger + DC cooling systemHuawei site power; available with 48 V / 100 Ah VRLA or ESM-48100A1 lithium bank, 50 A / 3000 W rectifier modules and UPEUeIP55 integrated cabinet with DC cooling system; supplied new-compatible; dimensions and U space confirmed per quotationOn enquiryOn enquiry
ICC500-HA1H-C5PowerCube 1000 ICC500 two-bay outdoor integrated cabinet, heat exchanger + DC air-conditioned battery bay, hybrid batteryPowerCube 1000 (V300R006); DCDU-400AD; ESU-A lithium plus FCB-A / TCB-A lead-acid1825 × 770 × 1305 mm; ≈315 kg; 14U customer space; equipment HEX 1500 W at 15 °C rise, battery PC500D DC air conditioner; up to 2 strings ESU-A plus 1 string FCB-A / TCB-A (400 Ah); front and rear maintenance; IP55, Class C; 0 to +50 °C with solar radiationOn enquiryOn enquiry
ICC500-HA2-C6PowerCube 1000 ICC500 two-bay outdoor integrated cabinet, heat exchanger + DC air conditioner, lead-acidPowerCube 1000 (V300R006); DCDU-300AN1; DCB-B / TCB-A / FCB-A lead-acid1825 × 770 × 1305 mm; ≈315 kg; 14U customer space; equipment HEX 1500 W at 15 °C rise, battery PC500D DC air conditioner; one string up to 650 Ah; IP55, Class C; −10 to +50 °C with solar radiationOn enquiryOn enquiry
ICC500-HA2-C7PowerCube 1000 ICC500 two-bay outdoor integrated cabinet, heat exchanger + DC air conditioner, lithiumPowerCube 1000 (V300R006); DCDU-300AN1; ESU-A2400Wh/D and /N lithium1825 × 770 × 1305 mm; ≈315 kg; 14U customer space; equipment HEX 1500 W at 15 °C rise, battery PC500D DC air conditioner; ESU-A max 400 Ah; IP55, Class C; 0 to +50 °C with solar radiationOn enquiryOn enquiry
ICC710-HA1-C1PowerCube 1000 ICC710 outdoor integrated cabinet, heat exchanger + DC air-conditioned lead-acid bay, config C1PowerCube 1000 G4 grid hybrid; ECC500S; up to 8 × R4850G2 / R4850N2; TCB-A / FCB-A lead-acidICC710 housing (1925 × 900 mm class); equipment HEX 150 W/K, battery PC500D DC air conditioner; 14U customer space; TCB-A / FCB-A max 650 Ah; DCDU-400AN2, 400 A; IP55; 0 to +45 °C with solar radiation (−20 °C with pre-heat device); front and rear maintenanceOn enquiryOn enquiry
ICC710-HA1-C2PowerCube 1000 ICC710 outdoor integrated cabinet, heat exchanger + DC air conditioner, 400 Ah lithium, config C2PowerCube 1000 D1-Advanced diesel hybrid and G2 grid hybrid; ECC500S; up to 8 × R4850S1; ATS-63A1 / 63A2 / 125C1; integrated diesel generator optionICC710 housing; equipment HEX 150 W/K, battery PC500D DC air conditioner; 14U customer space; ESU-A2400Wh/D or /N max 400 Ah; DCDU-400AN2, 400 A; IP55; −10 to +45 °C (D1) or 0 to +45 °C (G2) with solar radiationOn enquiryOn enquiry
ICC710-HA1-C3PowerCube 1000 ICC710 outdoor integrated cabinet, heat exchanger + DC air conditioner, 800 Ah lithium, config C3PowerCube 1000 D1-Advanced and G2; ECC500S; up to 8 × R4850S1 / R4850G2 / R4850N2ICC710 housing; equipment HEX 150 W/K, battery PC1000D DC air conditioner; 14U customer space; ESU-A2400Wh/D or /N max 800 Ah; DCDU-400AN2, 400 A; IP55; 0 to +45 °C with solar radiation (−20 °C with pre-heat)On enquiryOn enquiry
ICC710-HA1-C5PowerCube 1000 ICC710 outdoor integrated cabinet, heat exchanger + DC air conditioner, config C5PowerCube 1000 S2 solar + diesel; ECC500S; up to 8 × S4850G1 solar modules and R4850G2 / R4850N2; ESM-4850A1 lithiumICC710 housing; equipment HEX 150 W/K, battery PC1000D 1100 W DC air conditioner; 14U customer space; ESM-4850A1 up to 600 Ah; DCDU-400AN2; IP55; 0 to +45 °C with solar radiationOn enquiryOn enquiry
ICC710-HA1-C6PowerCube 1000 ICC710 large outdoor integrated cabinet, heat exchanger + DC air conditioner, config C6 (BOM 01075148)PowerCube 1000 hybrid power; controller and distribution unit included1925 × 900 × 950 mm (H × W × D); 400 A max DC; heat exchanger and DC air conditioner; BOM 01075148On enquiryOn enquiry
ICC710-HA1-C7PowerCube 1000 ICC710 large outdoor integrated cabinet, heat exchanger + DC air conditionerPowerCube 1000 rectifiers; ESM-48100B1 lithium1925 × 900 × 950 mm (1270 mm incl. door); <320 kg; 14U; HEX100 150 W/K + PC1500D-1 1500 W; max 12 lithium modules; IP55; 0 to +45 °COn enquiryOn enquiry
ICC710-HA1H-C5PowerCube 1000 ICC710 outdoor integrated cabinet with lead-acid / FCB-A battery bayFCB-A battery plus ESM-48100B11925 × 900 × 950 mm; <320 kg; 13U; HEX100 150 W/K + PC1500D-1 1500 W; 4 × ESM-48100B1 + 1 × FCB-A; IP55; 0 to +45 °C (−20 °C with heater)On enquiryOn enquiry
ICC710-HD1-C1PowerCube 1000 ICC710 outdoor integrated cabinet, heat exchanger + direct-ventilation battery bay, config C1PowerCube 1000 G4 grid hybrid; ECC500S; up to 8 × R4850G2 / R4850N2; TCB-A / FCB-A lead-acidICC710 housing; equipment HEX 150 W/K, battery direct ventilation; 14U customer space; TCB-A / FCB-A max 650 Ah; DCDU-400AN2, 400 A; IP55 equipment / IP34 battery; −10 to +40 °C with solar radiationOn enquiryOn enquiry
ICC720-HA1-C1PowerCube 1000 ICC720 outdoor integrated cabinet, heat exchanger + DC air conditioner, config C1Huawei −48 V site power, 48 V / 400 A embedded power system; sister codes ICC720-HA1-C2 / C3 and ICC720-A3-C148 V / 400 A; dimensions and remaining specification confirmed per quotationOn enquiryOn enquiry
ICC800-A1-C2PowerCube 1000 ICC800 outdoor integrated cabinet, DC air-conditioned, solar / hybrid variantPowerCube 1000 hybrid system; ESC800-A1; ETP48600-C5B1 power unit2000 × 800 × 800 mm; ≈250 kg empty; max 16 lithium modules; DC air conditioner; IP55; 0 to +45 °C; 0–4000 mOn enquiryOn enquiry
ICC900-HA1-C1PowerCube 1000 ICC900 outdoor integrated cabinet, HA1 climate, lithium, config C1PowerCube 1000 (V300R006); DCDU-400AN1; ESU-A2400Wh/D and /N lithiumESU-A max 600 Ah; DCDU-400AN1 distribution; dimensions and cooling capacity confirmed per quotationOn enquiryOn enquiry
ICC900-HA1-C2PowerCube 1000 ICC900 outdoor integrated cabinet, HA1 climate, lead-acid, config C2PowerCube 1000 (V300R006) standard co-site edition; DCDU-400AS; DCB-A (optional DCB-A1) lead-acidTwo strings of DCB-A, max 600 Ah per string; DCDU-400AS distribution; dimensions and cooling capacity confirmed per quotationOn enquiryOn enquiry
ICC900-HA1-C4PowerCube 1000 ICC900 outdoor integrated cabinet, two-compartment, air-conditioned, config C4PowerCube 1000; equipment compartment takes DC distribution, BBU and 19-inch equipment from mainstream vendorsTwo-compartment joined cabinet (equipment + battery); air-conditioning system; dimensions confirmed per quotationOn enquiryOn enquiry
MTS9300A-HX20A1MTS9300A outdoor equipment cabinet, 2 m, heat exchanger, 40UHuawei MTS9000A family; 300 A power subrack2000 × 750 × 750 mm excl. 150 mm base; <190 kg; 40U customer space; heat exchanger; IP55; Class COn enquiryOn enquiry
MTS9300A-XA10A3MTS9300A outdoor battery cabinet, 0.9 m, DC air-conditionedBattery cabinet for MTS9304A-HX10A1 split sites900 × 650 × 650 mm excl. 100 mm base; <65 kg excl. batteries; battery space 330 × 610 × 590 mm; PC300D air conditioner; IP55; Class COn enquiryOn enquiry
MTS9300A-XD10A2MTS9300A outdoor battery cabinet, 0.9 m, direct ventilationBattery cabinet for MTS9304A-HX10A1 split sites900 × 650 × 650 mm excl. 100 mm base; <65 kg excl. batteries; battery space 330 × 610 × 570 mm; direct ventilation; IP45; Class B onlyOn enquiryOn enquiry
MTS9304A-HA16A1MTS9000A outdoor power cabinet, 1.5 m, heat exchanger + DC air conditionerHuawei MTS9000A telecom power1500 × 650 × 650 mm excl. 100 mm base; <160 kg; 9U customer space; battery space 330 × 610 × 590 mm; 1500 W heat exchanger / PC300D air conditioner; IP55; Class COn enquiryOn enquiry
MTS9304A-HA2001MTS9000A outdoor power cabinet, 2 m, heat exchanger + DC air conditioner, 2001Huawei MTS9000A telecom power2000 × 650 × 650 mm excl. 100 mm base; ≤190 kg; 19U customer space; battery space 330 × 610 × 590 mm; heat exchanger / PC300D DC air conditioner; IP55 both compartments; Class COn enquiryOn enquiry
MTS9304A-HA20A1MTS9000A outdoor power cabinet, 2 m, heat exchanger + DC air-conditioned battery bayHuawei MTS9000A telecom power2000 × 650 × 650 mm excl. 100 mm base; ≤190 kg; 19U customer space; battery space 330 × 610 × 590 mm; 1500 W heat exchanger / PC300D DC air conditioner; IP55 / IP45; Class COn enquiryOn enquiry
MTS9304A-HD16A1MTS9000A outdoor power cabinet, 1.5 m, heat exchanger + direct ventilationHuawei MTS9000A telecom power1500 × 650 × 650 mm excl. 100 mm base; <150 kg; 9U customer space; battery space 330 × 610 × 590 mm; 1500 W heat exchanger / direct ventilation; IP55; Class COn enquiryOn enquiry
MTS9304A-HD2002MTS9300A outdoor power cabinet, 2 m, HXC300S heat exchanger + direct ventilation (BOM 01074838)Huawei MTS9300A telecom power; ESM-48100B1 lithium2000 × 650 × 650 mm incl. 100 mm base; HXC300S heat exchanger; Class C (not Class D); −20 to +45 °C with 1120 W/m² solar radiation; BOM 01074838 / 01074838-001On enquiryOn enquiry
MTS9304A-HD20A1MTS9000A outdoor power cabinet, 2 m, heat exchanger + direct-ventilation battery bayHuawei MTS9000A telecom power (V100R002C90); 19-inch customer equipment2000 × 650 × 650 mm excl. 100 mm base; ≤190 kg; 19U customer space; battery space 330 × 610 × 590 mm; heat exchanger / direct ventilation; IP55 equipment / IP45 battery; Class COn enquiryOn enquiry
MTS9304A-HX10A1MTS9000A outdoor power cabinet, 0.9 m, heat exchanger, single compartmentHuawei MTS9000A telecom power; combines with MTS9300A-XD10A2 / XA10A3 battery cabinets; battery PDB fitted900 × 650 × 650 mm excl. 100 mm base; <95 kg; 12U customer space; 1500 W heat exchanger; IP55; Class COn enquiryOn enquiry
MTS9510A-AX2005MTS9000A outdoor equipment cabinet, 2 m, DC air-conditioned, 40UHuawei MTS9000A family2000 × 750 × 750 mm excl. 150 mm base; ≤160 kg; 40U customer space; PC1500D-1 DC air conditioner; IP55; Class COn enquiryOn enquiry
MTS9514A-AM2001MTS9514A outdoor telecom cabinetBattery and telecom equipment installation2000 × 750 × 750 mm excl. 150 mm base; 18U user space plus 2 battery sets; LLVD 2 × 125 A + 3 × 63 A, BLVD 2 × 63 A, 2 × 32 A, 2 × 16 A; cooling and IP confirmed per quotationOn enquiryOn enquiry
MTS9514A-AM2002MTS9514A outdoor power cabinet, 2 m, DC air-conditioned, with battery spaceHuawei MTS9000A family; sister of MTS9514A-AM20012000 × 750 × 750 mm excl. 150 mm base; ≤190 kg; 19U (01074814) or 17U (01074814-002) customer space — by BOM; battery space 330 × 620 × 600 mm; PC1500D-1 DC air conditioner; IP55; Class COn enquiryOn enquiry
PowerCube-G G302APowerCube 1000 grid-hybrid integrated power and storage cabinetGrid / solar hybrid sites; 11U customer space1825 × 770 × 1250 mm; <1243 kg; 5 × 50 A; 31.2 kWh storage; heat exchanger + DC air-conditioned battery bay; IP55; −20 to +50 °COn enquiryOn enquiry
TBC300A-DCA5TBC300A outdoor battery cabinet, direct ventilation, north-typePairs with TP48200A-HX09A1 / HX09A5, stacked or side by side900 × 650 × 650 mm excl. base and protrusions, base 100 × 650 × 650 mm; ≤50 kg without batteries; direct ventilation with TCUA control box and heater; IP34; Class B environment; system operating range −10 to +45 °C with solar radiationOn enquiryOn enquiry
TMC11HAlso: WD2P048CAB29 (Ver.E)TMC11H outdoor transmission cabinet, 11U, heat exchanger (Ver.B / C / D / E)BTS3900A, BTS3900, DBS3900, BTS3900L / AL / C, BTS5900 / DBS5900; houses BBU3900 at −48 V DC700 × 600 × 480 mm; base 200 × 600 × 434 mm; ≤47 kg Ver.C/D/E, ≤57 kg Ver.B (excl. transmission equipment); 11U; heat dissipation at 50 °C ambient: 1800 W Ver.E, 1500 W Ver.D, 1050 W Ver.C, 700 W Ver.B; input −38.4 to −57 V DC; IP55; −40 to +50 °COn enquiryOn enquiry
TP48120A-HD15A1TP48120A outdoor power cabinet, 1.5 m, heat exchanger + direct-ventilation battery bay, 120 AHuawei −48 V site power; SMU06C; R4830N2 rectifiers (48 V / 30 A)1500 × 650 × 650 mm excl. base and door protrusion, base 100 × 650 × 650 mm; <120 kg excl. rectifiers and batteries; 120 A; equipment heat exchanger, battery direct ventilationOn enquiryOn enquiry
TP48120A-HD15A2TP48120A outdoor power cabinet, 1.5 m, heat exchanger + direct ventilation, with heaterHuawei −48 V site power; SMU06C; R4830N2 rectifiers1500 × 650 × 650 mm excl. base and door protrusion, base 100 × 650 × 650 mm; <120 kg excl. rectifiers and batteries; 120 A; heat exchanger, battery direct ventilation, heater fittedOn enquiryOn enquiry
TP48200A-D14A1TP48200A outdoor power cabinet, direct ventilation, 1.4 mHuawei −48 V site power1400 × 650 × 700 mm excl. base; direct ventilation >1500 W; >10U customer space; IP55 equipment bay / IP23 battery bay; −10 to +50 °COn enquiryOn enquiry
TP48200A-DT19C1TP48200A large outdoor power cabinet, 2 m, direct ventilation + TEC, C1Huawei −48 V site power; SMU monitoring2030 × 820 × 760 mm incl. 150 mm base; ≤200 kg excl. rectifiers and batteries; up to 12 kW; direct-ventilation equipment bay; floor / rooftop / wall mount; −10 to +45 °COn enquiryOn enquiry
TP48200A-DT19C2TP48200A large outdoor power cabinet, 2 m, direct ventilation + TEC, C2Huawei −48 V site power; SMU monitoring2030 × 820 × 760 mm incl. 150 mm base; ≤200 kg excl. rectifiers and batteries; max 12 kW; direct-ventilation equipment bay; −10 to +45 °COn enquiryOn enquiry
TP48200A-DT19D1TP48200A outdoor power cabinet, direct ventilation, 2 mHuawei −48 V site power2030 × 820 × 760 mm incl. base; <200 kg without rectifiers and batteries; IP55; direct ventilationOn enquiryOn enquiry
TP48200A-H15A3TP48200A integrated outdoor power cabinet, 1.5 m, heat exchanger + direct-ventilation battery bay, A3Huawei −48 V site power; 4 × 3000 W rectifiers1500 × 650 × 650 mm excl. base; <120 kg excl. rectifiers and batteries; max 12 kW (4 × 3000 W); equipment HEX 850 W, battery direct ventilation; 8U user space; 16U battery space (2 × 150 Ah); IP55 equipment / IP45 battery; AC 85–300 V, 1 × 63 A/3P input; −10 to +45 °COn enquiryOn enquiry
TP48200A-H15A5Also: TP48200A-H15A3, TP48200A-D15A1TP48200A integrated outdoor power cabinet, 1.5 m, heat-exchanger equipment bayHuawei −48 V site power; BTS and transmission equipment1500 × 650 × 650 mm excl. base; <120 kg; 4 rectifier slots, 11.6–12 kW; equipment bay HEX / battery bay direct ventilation; IP55 / IP45; −10 to +45 °C (D15A1 −40 °C)On enquiryOn enquiry
TP48200A-HD15A1TP48200A outdoor power cabinet, 1.5 m, heat exchanger + direct-ventilation battery bay, 200 AHuawei −48 V site power; SMU06C; R4850N2 rectifiers1500 × 650 × 650 mm excl. base and door protrusion, base 100 × 650 × 650 mm; <120 kg excl. rectifiers and batteries; 200 A; equipment heat exchanger, battery direct ventilationOn enquiryOn enquiry
TP48200A-HD15A2TP48200A outdoor power cabinet, 1.5 m, heat exchanger + direct ventilation, with heater, 200 AHuawei −48 V site power; SMU06C; R4850N2 rectifiers1500 × 650 × 650 mm excl. base and door protrusion, base 100 × 650 × 650 mm; <120 kg excl. rectifiers and batteries; 200 A; heat exchanger, battery direct ventilation, heater fittedOn enquiryOn enquiry
TP48200A-HT15A5Also: TP48200A-HT15A6, TP48200A-HT15B4TP48200A outdoor power cabinet, 1.5 m, heat exchanger + TEC, 200 AHuawei −48 V site power1500 mm excl. base × 650 × 650 mm; ≈120 kg excl. rectifiers and batteries; 48 V / 200 A; equipment bay heat exchanger, battery bay TEC air conditioner; 2-tier battery bayOn enquiryOn enquiry
TP48200A-HT19C1TP48200A large outdoor power cabinet, 2 m, heat exchanger + TEC, C1Huawei −48 V site power; SMU monitoring; 19-inch customer equipment2030 × 820 × 760 mm incl. 150 mm base; ≤200 kg excl. rectifiers and batteries; up to 12 kW; heat exchanger equipment bay, TEC04C battery cooling; equipment and battery compartments IP55; floor / rooftop / wall mount, not stackable; front access, bottom cabling; −10 to +45 °COn enquiryOn enquiry
TP48200A-HT19C2TP48200A large outdoor power cabinet, 2 m, heat exchanger + TEC, C2Huawei −48 V site power; SMU monitoring2030 × 820 × 760 mm incl. 150 mm base; ≤200 kg excl. rectifiers and batteries; max 12 kW; heat exchanger + TEC04C; IP55 both compartments; −10 to +45 °COn enquiryOn enquiry
TP48200A-HT19C3Also: TP48200A-HT19C4TP48200A large outdoor power cabinet, 2 mHuawei −48 V site power; 19-inch customer equipment2030 × 820 × 760 mm incl. 150 mm base; ≤200 kg without rectifiers and batteries; equipment and battery compartments IP55; floor / rooftop / wall mountOn enquiryOn enquiry
TP48200A-HX09A1TP48200A outdoor power cabinet, 900 mm split typeHuawei −48 V site power; combines with TBC300A-DCA5900 × 650 × 650 mm excl. 100 mm base; ≤75 kg without rectifiers; IP55; floor or wall mount, front accessOn enquiryOn enquiry
TP48200A-HX09A5TP48200A outdoor power cabinet, 900 mm split type, 12 kW rectifier setAvailable with SMU02C, S4850G1 3000 W and S4875G 4000 W rectifiers; stacks on TBC300A battery cabinet900 × 650 × 650 mm class (HX09 series); 12 kW rectifier configuration; IP55; cooling variant confirmed per quotationOn enquiryOn enquiry
TP48200E-H09A1Also: TP48200E-D09A1, TBC300A-DCA1, TBC300A-TCA1TP48200E split-type 900 mm outdoor power cabinets with TBC300A battery cabinetsHuawei −48 V site power900 × 650 × 650 mm; <70 kg excl. rectifiers and battery; heat exchanger (H) or direct ventilation (D); IP55 (battery cabinets IP34 / IP55); −40 or −10 to +45 °C by modelOn enquiryOn enquiry
TP48300A-DX15A1TP48300A outdoor power cabinet, 300 A, three-phase, direct ventilationHuawei −48 V site power, 220 / 380 V AC three-phase input1650 × 650 × 650 mm; 300 A; direct ventilation; weight and IP confirmed per quotationOn enquiryOn enquiry

Ordering notes

Give the full cabinet code with its suffix, because ICC330-H1-C8 and ICC330-HA1-C10 share a housing and differ entirely in what they will hold. State whether the site is AC- or DC-fed, the ambient range and solar exposure, the number of rectifier modules and the battery type and capacity you intend to fit, and whether the plinth or base frame is required. For TP48200A rollouts give the rectifier module (R48xx / S4850G1 / S4875G), the SMU model and the quantity per site so the cabinet, modules and monitoring are quoted as one line per site. For APM30H and TMC11H state the hardware version (Ver.C, D or E) because the fan unit, DCDU and rectifier shelf differ by version. Condition is stated per quotation — new, new surplus or refurbished with the cosmetic grade — and where a destination does not admit used network equipment we quote new. No list price is published; quotations are per cabinet with the configuration itemised — housing, climate unit, rectifier frame, modules, monitoring, batteries, plinth — and are prepared landed to the destination city where requested, with packed dimensions and weight stated for the freight line.

Lifecycle and availability

PowerCube 1000 (ICC330 / ICC710 / ICC800 with ESC cabinets, V300R007 and V300R008 manuals), PowerCube 500 and the PowerCube-G grid-hybrid cabinet are current Huawei site-power products. TP48200A and TP48300A outdoor power cabinets remain widely supplied new and as new surplus. APM30 / APM30H, TMC11H, IBBS200 and the BTS3900A / BTS3900AL cabinets belong to the 3900-series base-station generation and are supplied largely from refurbished and surplus stock, graded, with the hardware version stated. No official end-of-sale notice was found for any of these models; status is confirmed per quotation.

Configuring a PowerCube 1000 site — ICC plus ESC

A PowerCube 1000 site is an ICC equipment cabinet, optionally paired with an ESC battery cabinet of the same size series. The ICC carries the rectifier modules (R4875G5, R4850G5 or R4850G2), the site monitoring unit, the climate unit and either an internal battery bay or none. ICC330-H1-C8 gives the most equipment space (22U) and puts all batteries in an ESC330 next to it; ICC330-HA1-C10 and HD1-C5 give 8U and hold four ESM-48100B1/B2 or ESM-48150B1 lithium modules internally; ICC710-HA1-C7 gives 14U and twelve lithium modules; ICC800-A1-C2 is the solar and hybrid variant with sixteen lithium modules and an ETP48600 power unit.

Tell us the equipment to be housed in U, the battery autonomy required in hours and the site's power source — grid, grid-plus-solar or diesel-hybrid — and we will return the ICC and ESC combination, rectifier count and battery count rather than leave the buyer to match codes.

TP48200A power cabinets — the 12 kW site standard

The TP48200A family is the outdoor power cabinet most often requested for solar and hybrid rollouts: a 900 mm split type (TP48200A-HX09A1 / HX09A5, stacked on a TBC300A battery cabinet), a 1.5 m integrated cabinet (H15A3 / H15A5 / D15A1, heat-exchanger equipment bay with a ventilated battery bay, 11.6–12 kW rectifier set) and a 2 m cabinet (HT19C3 / HT19C4 / DT19D1, 2030 × 820 × 760 mm). A complete site is quoted as the cabinet, the rectifier modules (four 50 A slots on the 1.5 m type), the SMU02C monitoring unit and the battery strings. The TP48300A-DX15A1 is the 300 A, three-phase version for larger sites.

Replacing or extending a BTS3900A site

A BTS3900A outdoor site is a stack of 700 × 600 × 480 mm cabinets: the RFC radio cabinet, the APM30H power cabinet (heat exchanger, AC input to −48 V DC), the TMC11H transmission cabinet and one or two IBBS200 battery cabinets. Spares are ordered by cabinet and hardware version — a TMC11H Ver.E ships with FAN02E, DCDU12B or 12C, ELU and door sensor — and the quotation lists the fitted items rather than assuming them. Used APM30H and TMC11H units are graded and their fan units, heat exchangers and DCDUs tested before dispatch.

Equipment condition

New — factory-sealed, supplied through the manufacturer's own channel or a qualified distributor, with full manufacturer warranty.

New surplus — unused factory stock, original packaging where available, sourced from decommissioned projects or distributor inventory. Manufacturer warranty may have lapsed; CRS PLUS warranty applies.

Refurbished / tested — previously deployed equipment, cleaned, firmware-checked and functionally tested against the manufacturer's specification before shipment. CRS PLUS warranty applies.

Condition is confirmed in writing on every quotation before you commit to an order.

Warranty

Warranty terms vary by item, by condition and by the supplier the equipment is sourced from. They are stated in writing on the quotation, per line item, before you commit to an order.

Where equipment is supplied new through the manufacturer's own channel, the manufacturer's warranty applies and is passed to you.

Send us the part numbers you need and we will confirm warranty terms alongside availability, condition, lead time and price.

Refurbished stock — how it is graded and what ships

New and refurbished units are quoted side by side. For refurbished stock, the quotation answers the questions buyers ask first, in the order they ask them.

Cosmetic grade.Is the housing new?
Every refurbished unit is graded A, B or C and the grade is written on the quotation. Grade A: housing free of marks visible at arm's length, no discolouration, original labels intact. Grade B: light scuffing or minor marks, no cracks, labels legible. Grade C: visible wear or discolouration, functionally identical to A and B, offered only where the buyer has accepted it. Where an enclosure has been replaced with a new housing the quotation says so; a re-cased unit is never described as new.
Test coverage.Is it fully working?
Cabinets and enclosures are inspected and function-tested before dispatch: door seals and gaskets, locks and hinges, the heat exchanger or air conditioner run under power, fans and heaters, the rectifier shelf and monitoring unit powered up, busbars, breakers and surge protection checked, and the housing inspected for corrosion and impact damage. The scope of the test is stated on the quotation.
What ships with the cabinet.With plinth, keys and internal fittings?
The quotation lists exactly what ships: base frame or plinth, keys, rack mounting brackets, battery trays or fixing brackets, grounding busbar, cable-entry plates, cabin lighting and door contact, the climate unit, the rectifier frame and monitoring unit where fitted, and whether rectifier modules and batteries are included. Units are crated or palletised for sea or air freight and the packed dimensions and weight are stated for freight quotation.
Warranty on used stock.What warranty?
Warranty on refurbished equipment covers functional failure under normal use and is stated per line item on the quotation — the period, what it covers and how a return is handled — before you commit to an order.
Firmware state.Is the firmware in English, and is it locked?
The language of the shipped firmware and whether a unit is carrier-branded or carrier-locked is declared per lot. Where English firmware is required it is confirmed on the unit before dispatch, not assumed from the model number. Locked or operator-branded stock is declared as such and never described as open.
Licence state (OLT chassis and control boards).What about licences on a used OLT?
Second-hand OLT chassis and control boards are quoted with their licence and software state as received, stated on the quotation. CRS PLUS does not represent used chassis as carrying transferable licences; software licensing remains between the buyer and the manufacturer or integrator, and we recommend confirming the licensing position before relying on a used chassis for a live rollout.

Questions

Frequently asked questions

What does ICC330-H1-C4 actually contain?

It is a PowerCube 1000 ICC330 housing (1600 × 650 × 650 mm series) with a heat-exchanger-cooled equipment bay in configuration C4. Huawei's public manuals list it in the solution tables alongside ESC330 battery cabinets but do not publish a per-code specification, so the equipment space and battery fit for this exact code are confirmed per quotation; the C8, C10 and C5 siblings are fully specified in the table above.

Which lithium batteries fit the ICC cabinets, and can they ship inside?

ICC330 and ICC710 cabinets take ESM-48100B1, ESM-48100B2 and ESM-48150B1 lithium modules; ICC800 takes sixteen. Lithium batteries are dangerous goods in transit, so cabinets are normally quoted and shipped without them, with the batteries supplied as a separate DG consignment or sourced at destination.

What is included with a cabinet — rectifiers, batteries, climate unit, plinth?

Manufacturer weights are almost always quoted without rectifier modules and batteries, and dealer listings often say only "equipped cabinet". Every quotation from CRS PLUS itemises what ships: the housing, base frame or plinth, climate unit (heat exchanger, air conditioner or ventilation), rectifier frame and the number of modules fitted, monitoring unit, busbars, breakers and surge protection, battery trays and whether batteries are supplied. Ask for the packing list before comparing prices between sources.

Which climate variant suits a hot-climate site?

Heat-exchanger cabinets are sealed and suit most sites; direct-ventilation battery bays carry a lower ingress rating and suit cleaner, cooler locations; air-conditioned variants are specified where ambient temperature or solar load would otherwise shorten battery life. State the site's ambient range and whether the cabinet is in the sun and the quotation will say which variant is proposed and why.

Can I house another vendor's baseband or radios in the cabinet?

Site enclosures with open 19-inch space (Ericsson 6130/6140/6150, Vertiv ECM3, Eltek Type 3/4, Delta OutD, Nokia ACOA/ACOB) accept any 19-inch, −48 V DC equipment; what must be checked is the DC breaker count and rating, cable entry, heat load against the climate unit and the alarm interface. Platform-specific housings (Huawei APM30H/TMC11H, ZTE BS8900 cabinets, Nokia AMOB/AMOD) are built around their own baseband and are quoted with that platform.

How are cabinets shipped and how long does it take?

Cabinets are crated or palletised and normally move by sea because of volume; air freight is quoted where the schedule demands it. Dispatch time and transit time are stated separately on the quotation. Lithium batteries are dangerous goods in transit, so cabinets are usually shipped without batteries unless DG-compliant freight is arranged.

What warranty applies, and what does it cover on used cabinets?

Warranty terms are stated per line item on the quotation, for new and refurbished cabinets alike. On refurbished units the warranty covers functional failure of the climate unit, power frame and monitoring under normal use; the period, exclusions and return procedure are set out in writing before you commit to an order.

Will the footprint fit my existing plinth?

Footprints differ between generations even within one vendor — an RBS 6102 is 1300 × 700 mm and an Enclosure 6150 800 × 700 mm; a Huawei ICC330 is 650 × 650 mm and an ICC710 900 × 950 mm. Send the existing plinth or base-frame dimensions and the anchor pattern with the enquiry and the quotation will confirm fit or propose an adapter frame.

Manufacturer names, product names and part numbers are the property of their respective owners and are used here for identification purposes only. CRS PLUS sources these products through its qualified supplier base and holds no distributor, reseller or agency appointment from any manufacturer listed.

This catalogue is compiled from our supplier network's available inventory and from manufacturer product documentation, and is reviewed monthly. Listing does not indicate stock held by CRS PLUS — availability, condition and lead time are confirmed per enquiry. Last reviewed: 7 November 2026.

Need a part number from Outdoor Cabinets & Enclosures?

A structured offer follows within 72 hours.

Sending a full specification or a BOQ? Use the full RFQ form.